Solar checker

Your panels. The right connection.

Choose a panel and check its electrical limits before connecting it.

Browse solar panels ↗
Foldable solar panel on grass connected to a portable power device
01

Which panel?

100watts
EcoFlow 100W Flexibleflexible
Panel data & source Manufacturer profile

We filled in the electrical limits from EcoFlow’s official manual for this exact 100W flexible model.

Checked:

Review or edit the valuesAlready filled in

Take these values from the exact panel label or datasheet. Do not guess a missing temperature coefficient.

What do these terms mean? →
02

Your panel layout

Panels per stringIn series · increases voltage
1
Identical stringsSplit over inputs where modeled
1
1 × 11 identical panels in total
How are the strings connected?

Panels in a string are connected in series. The calculation distributes identical strings across the station’s modeled inputs; extra strings on one input are parallel. This is not a wiring diagram.

Only identical panels and equal string lengths are modeled. Fuses, cable gauge, grounding and local installation rules need a separate check.

Compare the inputs

Which station fits the calculation?

Sorted by modeled limits. Not a purchase recommendation or wiring approval.

Within modeled limitsEcoFlow

DELTA 3 Plus

11–60 V · 15 A per input

Why this result?
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 15 AWithin limit
Power per used input
100 WLimit: ≤ 500 WWithin limit

Two independent 11–60V inputs; each accepts 15A and 500W, for 1,000W total.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → XT60i

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile ↗
Within modeled limitsAnker SOLIX

C1000 Gen 2

11–60 V · 14.5 A per input

Why this result?
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 8.2 AWithin limit
Power per used input
100 WLimit: ≤ 600 WWithin limit

One XT60i input: 11–28V at 8.2A, then 29–60V at 14.5A, with 600W maximum.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → XT60i

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile ↗
Within modeled limitsJackery

Explorer 1000 v2

16–60 V · 10.5 A per input

Why this result?
Charging voltage
17.1 VLimit: 16–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 10.5 AWithin limit
Power per used input
100 WLimit: ≤ 200 WWithin limit

Two parallel DC8020 inputs; each supports 200W and 10.5A, for 400W total with matched panel groups.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → DC8020

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile ↗
All power stations 7
EcoFlow DELTA 3 PlusWithin modeled limits
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 15 AWithin limit
Power per used input
100 WLimit: ≤ 500 WWithin limit

Two independent 11–60V inputs; each accepts 15A and 500W, for 1,000W total.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → XT60i

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Anker SOLIX C1000 Gen 2Within modeled limits
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 8.2 AWithin limit
Power per used input
100 WLimit: ≤ 600 WWithin limit

One XT60i input: 11–28V at 8.2A, then 29–60V at 14.5A, with 600W maximum.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → XT60i

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Jackery Explorer 1000 v2Within modeled limits
Charging voltage
17.1 VLimit: 16–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 10.5 AWithin limit
Power per used input
100 WLimit: ≤ 200 WWithin limit

Two parallel DC8020 inputs; each supports 200W and 10.5A, for 400W total with matched panel groups.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → DC8020

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Jackery Explorer 2000 v2Within modeled limits
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 12 AWithin limit
Power per used input
100 WLimit: ≤ 200 WWithin limit

Two DC8020 inputs share a 400W ceiling. Jackery documents 11–16V at 8A and 16–60V at 12A per high-voltage input, with 21A combined maximum.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → DC8020

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Jackery Explorer 2000 PlusWithin modeled limits
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 8 AWithin limit
Power per used input
100 WLimit: ≤ 700 WWithin limit

Two DC8020 inputs share a 1,400W ceiling. Jackery documents 11–17.5V at 8A and 17.5–60V at 12A per input, with 24A combined maximum.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → DC8020

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Anker SOLIX F3000Needs a manual check
Charging voltage
17.1 VLimit: 11–165 VWithin limit
Voltage in cold weather
22.6 VLimit: < 165 VWithin limit
Current per used input
5.9 ALimit: ≤ 17 AWithin limit
Power per used input
100 WLimit: ≤ 1,600 WWithin limit

This check models the 11–165V, 17A and 1,600W high-PV input. A separate low-PV input accepts 11–60V, 17A and 800W; together Anker lists 2,400W total.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Only the listed primary input is modeled. This station has another, different PV input that this result does not model.

Cable route — not yet verifiedMC4 → High-PV input

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Anker SOLIX F3800Needs a manual check
Charging voltage
17.1 VLimit: 11–60 VWithin limit
Voltage in cold weather
22.6 VLimit: < 60 VWithin limit
Current per used input
5.9 ALimit: ≤ 27 AWithin limit
Power per used input
100 WLimit: ≤ 1,200 WWithin limit

Two XT60 inputs accept up to 1,200W each. Current bands depend on firmware: newer firmware lists 10A at 11–15V and up to 27A at 15–60V; verify the installed firmware before designing an array.

Short-circuit current (Isc): 6.3 A per used input. Still verify protection and wiring requirements.

Calculation assumes: 1 identical strings across 1 used input(s).

Cable route — not yet verifiedMC4 → XT60

Check the exact adapter, polarity, fuses and cable ratings in both manuals.

Modeled power ceiling: 100 W. A limit, not a forecast of solar yield or permission to connect.

Product profile →
Privacy
YOUR POWER SETUP

Cookies

May we use Google Analytics cookies to understand which pages are useful? Only with your permission. We do not send calculator entries. You can change your choice below at any time. Cookie policy · Privacy